The cooling capacity of the Hengde HC-25A modular air cooled chillers are 60W.
Model :
HC-25ACooling Capacity :
75 Kw, 25 hpInput Power :
24.36 KwRefrigerant Type :
R22, R134a, R407c, 404a, 410aCompressor Power :
18.75 KwPump Power :
2.25 KwHengde's HC-25A air-cooled chiller, with its 25hp cooling capacity (also called 75kw air cooled chiller, 20 ton air cooled chiller or 25hp air cooled chiller), is widely utilized in sectors such as blow molding,extrusion,die casting,tire seals, reactor, food & beverage, packing and printing. It accurately provides the temperature essential for modern industrial manufacturing, thereby greatly enhancing production efficiency and product quality.
Model And Technical Parameter:
Model | Unit | HC-25A Modular Air Cooled Chillers System | |
Cooling Capacity | Kcal/h | 50hz | 64500 |
60hz | 77250 | ||
Kw | 50hz | 75 | |
60hz | 90 | ||
Input Power | Kw | 24.36 | |
Power Supply | 3 phs, 380V, 50hz. (Can be customized) | ||
Refrigerant | Type | R22, R134a, R407c, 404a, 410a | |
Control Mode | Outside the balanced thermal expansion valve) | ||
Compressor | Type | Hermetic Scroll Type (Piston) | |
Power | Kw | 18.75 | |
Condenser | Type | Efficient Copper Tube Set Of Aluminum Finned + Low Noise External Rotor Fan | |
Cooling Air Flow | m³/h | 25000 | |
Evaporator | Type | Tank Coil (Dry Type Shell and Tube / Stainless Steel Plate Evaporator) | |
Frozen Water Flow | m³/h | 11.69 / 13.79 | |
Water Tank Capacity | L | 340 | |
Pipe Diameter | Inch | 2-1/2'' | |
Pump | Power | Kw | 2.25 |
Maximum Head | M | 20 | |
Safety Protection |
|
|
Compressor Overheating、Over Current、High and Low Pressure 、Over Temperature、Traffic、Phase Sequence / Phase Loss Protection、Exhaust Overheating Protection |
Size (L*D*H) | mm | 1800*1100*1400 | |
Weight | Kg | 850 |
Notes:
If this model is not suitable for your existing products, please inform us of the following information, and we can accurately recommend a suitable model to you:
1. Cooling capacity (if you don't know the specific cooling capacity, please kindly provide the machine flow, inlet and outlet temperature of the equipment);
2. Application industry;
3. Ambient temperature;
4. Refrigerant type: R134a, R407c, R22 or other, please specify;
5. Voltage (Can be customized);
6. Any other special requirements, such as pump flow, pressure requirements, explosion-proof requirements, etc.
Our Advantages:
1 - The Factory We Own
2 - The Partners we cooperate.
3 - The Glowing Reviews from Numerous Customers.
4 - The Abundant Industry Cases We Present.
Hot Tags :