The 404a water cooled chillers' cooling capacity are 5.64kW.
Model :
HL-08WLCooling Capacity :
5.64kwInput Power :
6.75kwRefrigerant Type :
R22 , R134a , R407c , 404a, 410aCompressor Power :
6KwPump Power :
0.75KwHengde low temperature 404a water cooled chillers are applicable to products in need of fast cooling, like in the chemical, biological, pharmaceutical, freeze drying, food, and military - industrial fields. The compressors and key refrigeration parts are all of international famous brands. The low temperature 404a water chillers of Hengde HL-08WL model can achieve a minimum temperature of -25℃.
-25℃ 8hp Water cooled Chiller Features:
(1). The refrigerant can be adjusted according to the customer's specific situation.
(2). The operation interface is in Chinese and English, simple and easy to operate.
(3). RS485 communication function helps achieve automatic management (selected).
(4). Customization of an explosion-proof model is also possible.
(5). Using high-efficiency evaporators and condensers can lead to saving more than 30% of energy.
(6). With complete safety protection, fault display, repair, and maintenance don't require professional help.
(7). The compressors of the units are of imported brands, namely French Maneurop, American Copeland/Carrier, and German Bitzer, which are medium and low temperature compressors.
Model And Technical Parameter:
Model | Unit | HL-08WL Low Temperature 404a Water Cooled Chillers | |
Cooling Capacity | Kcal/h | 50hz | 4849 |
60hz | 5819 | ||
Kw | 50hz | 5.64 | |
60hz | 6.77 | ||
Input Power | Kw | 6.75 | |
Power Supply | 3 phs, 380V, 50hz. (Can be customized) | ||
Refrigerant | Type | R22, R134a, R407c, 404a, 410a | |
Control Mode | Outside the balanced thermal expansion valve | ||
Compressor | Type | Fully enclosed vortex type (Piston) | |
Power | Kw | 6 | |
Condenser | Type | Shell and Tube | |
Cooling Water Flow | m³/h | 6.2 / 7.44 | |
Pipe Diameter | Inch | 1-1/2'' | |
Evaporator | Type | Shell and Tube / Stainless Steel Plate | |
Water Flow | m³/h | 2.73 / 3.27 | |
Pipe Diameter | Inch | 1'' | |
Pump | Power | Kw | 0.75 |
Maximum Head | M | 18 | |
Safety Protection |
|
|
Compressor Overheating、Over Current、High and Low Pressure 、Over Temperature、Traffic、Phase Sequence / Phase Loss Protection、Exhaust Overheating Protection |
Our Advantages:
1 - The Factory We Own
2 - The Partners we cooperate.
3 - The Glowing Reviews from Numerous Customers.
4 - The Abundant Industry Cases We Present.
Hot Tags :